Description
Permission RCM markc UL us – Listed (OL)
CE certificate (see declaration of conformity) acc. to EU-EMV Directiveacc. to EU-RoHS Directive
KC-mark KC-EMV
Certified awarding point UL E322346
Material information RoHs compliant
Measured parameter Voltage
Signal range 0 – 10 V
ambient temperature [??C] 0 to 50
Sampling interval type [ms] 1
Accuracy FS [%FS] 0,5
Repeatability in ?I %FS [%FS] 0,2
Control output 2 x PNP or 2 x NPN switchable
Switch function Freely programmable
Switching element function Opener/closer switchable
Max. output current [mA] 100
Short circuit resistance yes
Report IO-Link
IO-Link, report Device V 1.1
IO-Link, profile Smart sensor profile
IO-Link, function classes Teach channelDiagnosisIdentificationBinary data channel (BDC)Process data variables (PDV)
IO-Link, communication mode COM2 (38.4 kBaud)
IO-Link, SIO mode support yes
IO-Link, port type A
IO-Link, process data width OUT 0 Bytes
IO-Link, process data width IN 5 Bytes
IO-Link, process data contents IN 14 bit PDV (measurement InA)14 bit PDV (measurement value InB)2 bit BDC (measurement monitoring)
IO-Link, minimum cycle time 5 ms
IO-Link, data memory needed [Byte] 500
Operating voltage range DC [V] 15 to 30
Reverse polarity protection for all electrical connections
Electrical connection 1, connection type Plug
Electrical connection 1, connection technology Wiring diagram L1J
Electrical connection 1, number of pins / wires 4
Electrical connection 2, connection type 2x socket
Electrical connection 2, connection technology Wiring diagram EC
Electrical connection 2, number of pins / wires 4
Fastening type Front panel integrationWith Wall / flat holder
Product weight [g] 23
Housing material PA reinforced
Display type Illuminating LCD Multiple
Setting options IO-LinkTeach-In??ber Display und Tasten
Tamper-proof fuse IO-LinkPIN code
Protection category IP40
Corrosion resistant class KBK 2 – moderate corrosion stress
Reviews