Description
Design Angular
Based on standard EN 60947-5-2VDI/VDE 3845
Permission RCM markc UL us (OL)
CE certificate (see declaration of conformity) to EU EMC directive
KC-mark KC-EMV
Material information LABS containing materials includedRoHs compliant
Measurement principle Inductive
ambient temperature [??C] -25 to 70
Control output As interface
Switching element function Opener/closer switchable
Max. switching frequency [Hz] 100
Max. switch off voltage DC [V] 26,4
Max. output current DC [mA] 100
Max. switching capacity DC [W] 2,5
Report As interface
As interface, report version V3.0
As interface, addressing area 1A … 31A (0)1B … 31B
As interface, product identification IO code: DID-Code: AID1 code: 7ID2 code: E
Operating voltage range DC [V] 26.5 to 31.6
Empty run current [mA] <= 35 mA
Electrical connection: input M12x14 pinPlug
Electrical connection: outlet M12x14 pinsocket / container / ??.
installation position arbitrary
Product weight [g] 70
Housing material PBT
Screws material High-alloyed stainless steels
Operation-readiness display LED green
Switching status indicator LED yellow
Status display LED yellow = Valve switching statusLED red = Wire break / short circuit on valve
Bearing temperature [??C] -25 to 70
Protection category IP67
Shock resistance Shock test with degree of severity 2 to FN 942017-5 and EN 60068-2-27
Oscillation strength Transport use test with severity level 2 to FN 942017-4 and EN 60068-2-6
Degree of contamination 3
Reviews