How to Choose an SMC ITV Electro-Pneumatic Regulator: Body Size, Set Pressure, and Input Signal
2026-11-29When you need to set compressed-air outlet pressure steplessly from an electrical signal, SMC’s ITV electro-pneumatic regulator is the series usually considered. It converts a current, voltage or communication signal into a corresponding outlet pressure. The figures below are taken from SMC’s Chinese catalogue CAT.CS60-15G B, Electro-Pneumatic Regulator / Electronic Vacuum Regulator, ITV Series, and are consistent with the official English WEB Catalog page for the same ITV series. This article covers only the positive-pressure ITV0000 and ITV1000/2000/3000 families in that catalogue, plus the electronic vacuum regulators ITV009□ and ITV209□ in the same document. The high-flow ITV1100/2100/3100 line and the high-pressure ITVH and ITVX regulators have their own catalogues; do not mix those ratings with the series discussed here.
Start with body size, flow and port size
On the catalogue cover, at a set pressure of 0.6 MPa and a supply pressure of 1.0 MPa, the stated maximum flow is 6 L/min (ANR) for ITV0000, 200 L/min (ANR) for ITV1000, 1500 L/min (ANR) for ITV2000, and 4000 L/min (ANR) for ITV3000. 0.6 MPa lies only within the adjustable range of the 0.9 MPa models (pressure-range code 5). Do not apply that cover figure to the 0.1 MPa or 0.5 MPa models. The standard specifications also state that these characteristics are for static conditions; if air is consumed on the outlet side, the pressure may vary.
Check the port size at the same time. ITV0000 is the compact type, with built-in one-touch fittings on a single unit (metric ø4 or inch ø5/32″), and it can be manifolded on a DIN rail (up to 10 stations). Because a manifold shares common supply and exhaust, different pressure ranges must not be mixed. ITV1000 ports are 1/8 and 1/4; ITV2000 ports are 1/4 and 3/8; ITV3000 ports are 1/4, 3/8 and 1/2. Thread types are Rc, NPT, NPTF or G. An ITV cannot raise outlet pressure above the available supply. If the supply is too low, size a booster separately; see SMC VBAF vs VBA booster regulators.
Then choose the set-pressure range
Each positive-pressure family has three set-pressure ranges. For ITV0000: ITV001□ is 0.001 to 0.1 MPa, ITV003□ is 0.001 to 0.5 MPa, and ITV005□ is 0.001 to 0.9 MPa. For ITV1000/2000/3000: ITV□01□ is 0.005 to 0.1 MPa, ITV□03□ is 0.005 to 0.5 MPa, and ITV□05□ is 0.005 to 0.9 MPa. Minimum supply pressure is the set pressure plus 0.1 MPa in every case. Maximum supply pressure is 0.2 MPa on the 0.1 MPa models and 1.0 MPa on the others. If you select a 0.1 MPa model, the supply must not exceed 0.2 MPa.
For vacuum pressure, use the electronic vacuum regulators instead: ITV009□ is −1 to −100 kPa, and ITV209□ is −1.3 to −80 kPa. Do not try to run a positive-pressure ITV “in reverse” as a vacuum regulator.
Input signal, monitor output and power supply
The usual analogue inputs are current type DC 4 to 20 mA and DC 0 to 20 mA (both sink) and voltage type DC 0 to 5 V and DC 0 to 10 V. The catalogue states that a 2-wire DC 4 to 20 mA connection cannot be used; a 24 VDC ±10% or 12 to 15 VDC power supply is still required. ITV1000/2000/3000 also offer 4-point or 16-point preset input, 10-bit parallel digital input, and CC-Link, DeviceNet®, PROFIBUS DP, RS-232C or IO-Link. Communication types, 16-point preset input and 10-bit digital input are limited to 24 VDC.
On ITV0000, the analogue monitor output is DC 1 to 5 V (output accuracy within ±6% F.S.). On ITV1000/2000/3000 you choose one of analogue DC 1 to 5 V, analogue DC 4 to 20 mA (sink), or a switch output (NPN or PNP). Linearity, hysteresis, repeatability and sensitivity are the same in both specification tables: linearity within ±1% F.S., hysteresis within 0.5% F.S., repeatability within ±0.5% F.S., and sensitivity within 0.2% F.S.
| Series | Set pressure range | Port size | Max. supply pressure | Enclosure |
|---|---|---|---|---|
| ITV0000 | 0.001 to 0.1 / 0.5 / 0.9 MPa | Built-in one-touch fittings | 0.2 MPa on 0.1 MPa models; 1.0 MPa otherwise | IP65 equivalent |
| ITV1000 | 0.005 to 0.1 / 0.5 / 0.9 MPa | 1/8, 1/4 | Same as above | IP65 |
| ITV2000 | 0.005 to 0.1 / 0.5 / 0.9 MPa | 1/4, 3/8 | Same as above | IP65 |
| ITV3000 | 0.005 to 0.1 / 0.5 / 0.9 MPa | 1/4, 3/8, 1/2 | Same as above | IP65 |
| ITV009□ | −1 to −100 kPa | Built-in one-touch fittings | (vacuum type; see that series table) | IP65 equivalent |
| ITV209□ | −1.3 to −80 kPa | 1/4 | (vacuum type; see that series table) | IP65 |
For ITV0000 and ITV009□ the catalogue says “IP65 equivalent”; to use the product under that condition, fit a connector and tubing to the breather hole. ITV1000/2000/3000 and ITV209□ are rated IP65; connect a fitting and tubing to the solenoid EXH port before use. Ambient and fluid temperature is 0 to 50°C (no condensation). The ITV1000 series is a grease-free specification for parts in contact with the fluid.
Other typenumber choices
For ITV1000/2000/3000, the how-to-order table also requires a power-supply voltage, monitor output, thread and port, cable connector and bracket. Power supply is 24 VDC or 12 to 15 VDC; as noted above, communication types, 16-point preset input and 10-bit digital input are 24 VDC only. The cable connector can be a straight 3 m type, a right-angle 3 m type, or omitted; the right-angle type is not available with 10-bit digital input. Flat and L-shaped brackets are packed with the product when selected. Approximate weight without options is about 250 g for ITV1000, 350 g for ITV2000 and 645 g for ITV3000; add 50 g for the digital input type and 70 g for the 16-point preset input type. Communication-type weights are listed separately in the communication specification table and differ from these figures.
The precautions also require one power supply unit per product. The power-supply GND and the signal COMMON are connected internally; supplying several electro-pneumatic regulators from one power unit may cause a return current and prevent normal operation. A right-angle cable can be led out in one direction only. When connecting it, turn only the lock ring; do not twist or force other parts of the connector.
Supply air, power-off behaviour and installation
The specific product precautions require an air filter of 5 μm or finer close to the supply; if the air carries a large amount of condensate, install an aftercooler, air dryer or drain separator. For purity classes see ISO 8573-1 compressed air quality classes; for the filter chain see how to choose an SMC AFF, AM or AMD filter. Do not install a lubricator on the supply side, or malfunction may result. If the downstream equipment needs lubrication, fit the lubricator on the outlet side of this product.
If power is shut off while the unit is pressurised, the outlet pressure is held only temporarily and is not guaranteed to remain. To exhaust, first reduce the set pressure, then shut off the power and release residual pressure with a residual-pressure relief valve or similar. If supply pressure is cut while the unit is still powered, the built-in solenoid valves continue to operate and may make a noise; always shut off this product’s power before shutting off the supply. The catalogue also states that this product must not be used as a shut-off valve: if supply pressure is applied with the power off, the outlet pressure may, after some time, rise to a level comparable to the supply pressure. Shut off the supply when the unit is taken out of service. On ITV1000/2000/3000, outlet pressure cannot be released completely below 0.005 MPa (below −1.3 kPa on the vacuum types). If the pressure must fall to 0 MPa, install a 3-port valve or similar on the outlet to discharge the residual pressure.
FAQ
Can I wire 4 to 20 mA as a 2-wire loop?
No. The catalogue note says a 2-wire DC 4 to 20 mA connection cannot be used. The required power supply voltage is still 24 VDC or 12 to 15 VDC.
Will outlet pressure stay at the last setpoint after a power cut?
Not in the sense of a guaranteed hold. The catalogue describes a temporary hold only, and says it is not guaranteed. To exhaust or return to atmospheric pressure, reduce the setpoint first, then cut the power and use a residual-pressure relief valve as the precautions describe.
Can an ITV be used as a shut-off valve?
No. The design and selection precautions state that this product must not be used as a shut-off valve. With the power off, outlet pressure may rise toward the supply pressure, so the supply should be shut off when the unit is stopped.
Always confirm specifications against the current official catalogue: CAT.CS60-15G B (PDF) and the official English series page for the ITV electro-pneumatic regulator. For a part-number check or an RFQ, email doskee@dustry.ltd.